URGENT! The correct fuse in plugs.... (2024)

A

admin_exported

New member
Aug 10, 2019
2,556
4
0
Visit site
  • Nov 23, 2009
  • #1

Evening, i have taken delivery today of some mains cables for various bits of kit. I did specify the gear that the mains leads would be feeding when i ordered. They have all come with 13 amp fuses. Now only one lead that i am replacing is actually 13amp. The other two are 5 amp. One for the TV and one for the sub.

My question is, when they are plugged into a mains conditioner, will this be ok or do they need to have the correct 5 amp fuse in the plug?

Ta

daveh75

Well-known member
Jul 31, 2008
1,114
503
20,070
Visit site

  • Nov 23, 2009
  • #2

Yes it's important from a safety point of view.The fuse isn't there to protect the equipment,but the cable itself, from potential overload should a short/fault occur!!!

Just replace the fuses in the new leads with the 5A ones from your equipments original leads.

A

Anonymous

Guest
  • Nov 23, 2009
  • #3

Thanks

I only actually have to replace one at this moment in time due to the fact that the one for the tv doesnt fit in the tv properly and hence doesnt work at all!!

Not happy at all.

K

kena

Well-known member
May 28, 2008
104
0
18,590
Visit site

  • Nov 23, 2009
  • #4

Odd I know but RA only sells 13a fuses doesn't do 5 or 10 , I bought Audiophile fuses for correct rating from flea-bay

A

Anonymous

Guest
  • Nov 23, 2009
  • #6

Thanks fellas. My old man has also told me 13 would be fine and that the RC would trip if there was any issu anyway........

A

Anonymous

Guest
  • Nov 23, 2009
  • #7

kena:

Odd I know but RA only sells 13a fuses doesn't do 5 or 10 , I bought Audiophile fuses for correct rating from flea-bay

As daveh75 says the fuse only protects the cable from the plug to the equipment it is feeding. So RA not supplying 5 or 10amp fuses is fine as long as the leads they offer are rated 13A or more.

Do the audiophile fuses make a noticable difference?

daveh75

Well-known member
Jul 31, 2008
1,114
503
20,070
Visit site

  • Nov 23, 2009
  • #8

scowl:
If the new mains leads (from a reputable mfr) were supplied with 13A fuses one has to assume that the leads are rated at 13A or above. So no, the 5A should not have to be fitted.That's actually a good point,and something i overlooked

URGENT! The correct fuse in plugs.... (48)

G

gpi

New member
Mar 29, 2008
23
0
0
Visit site
  • Nov 24, 2009
  • #9

A guide that I always remember is if the component or appliance operates at 750 watts or higher (e.g. a kettle), it needs a 13 amp fuse. Anything below 750W needs a 5 or 3 amp fuse. The wattage something runs at will always be printed clearly on the label on the rear or back.

H

hammill

New member
Mar 20, 2008
212
0
0
Visit site
  • Nov 24, 2009
  • #10

gpi:A guide that I always remember is if the component or appliance operates at 750 watts or higher (e.g. a kettle), it needs a 13 amp fuse. Anything below 750W needs a 5 or 3 amp fuse. The wattage something runs at will always be printed clearly on the label on the rear or back.I=P/V. So a 750 watt appliance would need a fuse of 750/230 = 3.26 amps. Rounding up to the nearest commonly available value gives 5 amps.

G

gpi

New member
Mar 29, 2008
23
0
0
Visit site
  • Nov 24, 2009
  • #11

From wikipedia:

3 A fuses are intended mainly for small load (less than 750 W) appliances, such as radios and lights. 13 A fuses are for larger load (less than 3.2 kW) appliances, such as heating and heavy-duty electric motors.

BS 1362 requires that plug fuses with any other current rating be marked in black. 5 A fuses are also commonly used for medium load 1250 W max. appliances such as desktop computers and TV sets. Ratings of 1, 2, 7, and 10 amperes are also produced but rarely used. (1 A, as found in some shaving-socket adapters, is 20 mm long (BS 646), but a BS 1362 version does exist).

Rewirable BS 1363 plugs are always sold fitted with a fuse, usually 13 A. This fuse must be changed if fitting the plug to an appliance or flex which requires a fuse with a smaller rating. Plugs with smaller fuse sizes already fitted are sold but are not as common.

Well there's my theory out the window, doh.

K

kena

Well-known member
May 28, 2008
104
0
18,590
Visit site

  • Nov 24, 2009
  • #12

scowl:kena:

Odd I know but RA only sells 13a fuses doesn't do 5 or 10 , I bought Audiophile fuses for correct rating from flea-bay

As daveh75 says the fuse only protects the cable from the plug to the equipment it is feeding. So RA not supplying 5 or 10amp fuses is fine as long as the leads they offer are rated 13A or more.

Do the audiophile fuses make a noticable difference?

Not that I noticed, but due to the the low cost it's not a big deal and I was using RA fuses anyway..

W

wireman

New member
Aug 6, 2009
17
0
0
Visit site
  • Nov 24, 2009
  • #13

daveh75:Yes it's important from a safety point of view.The fuse isn't there to protect the equipment,but the cable itself, from potential overload should a short/fault occur!!!

That is technically right according to the IEE and BS7671 (the electricians' standards) - the principle purpose of the fuse is there to protect the cable. But the fuse also affords a degree of protection to the equipment, and a lower rated one will disconnect the circuit sooner should a fault occur. Although most electronics have even lower rated fuses internally to protect the item, by using a 13A fuse in the plug of a device drawing probably less than 2 amps means the equipments' internal fuse is most likely to fail first, requiring a trip to the repair shop. So even if your fancy mains cable is capable of feeding a small sub-station, it's worth changing the fuse for a lower rated one more in keeping with the current draw of the item itself - typically 5A for most source components, and using 13A only for larger power amplifiers and AV receivers.

Me? I've bypassed all my fuses and have my equipment hard-wired into dedicated circuits and protected by MCB's (miniture circuit breakers), which operate more quickly than fuses, and are generally acknowledged to sound better than fuses too. If you ask any of the people who actually make these fancy mains cables, that's generally what they've done in their own homes too. The point here is that all fuses (however "audiophile" they may pretend to be) do have a 'sound' and are inferior to alternative methods of protection... I even have a friend who polishes his fuses with Duraglit, and swears they sound better!

A

Anonymous

Guest
  • Nov 25, 2009
  • #14

Wireman,

I am suprised that circuit breakers sound better than fuses. CBs are more complex and put an inductance directly in-line. I would have thought this would cause phase-shifty current laggy problems.

Barring the old re-wireable fuse, circuit breakers are still generally regarded as slower acting than fuses.

A

Anonymous

Guest
  • Nov 25, 2009
  • #15

Some interesting stuff gents.

I have now swapped all the fuses in all cases to the ones that were in the original leads.

URGENT! The correct fuse in plugs.... (58)

W

wireman

New member
Aug 6, 2009
17
0
0
Visit site
  • Nov 25, 2009
  • #16

scowl:

Wireman,

I am suprised that circuit breakers sound better than fuses. CBs are more complex and put an inductance directly in-line. I would have thought this would cause phase-shifty current laggy problems.

Barring the old re-wireable fuse, circuit breakers are still generally regarded as slower acting than fuses.

If you look at the up-market range of mains conditioners from people like Isotek and Isol8, you'll see they use circuit breakers on their devices in preference to fuses. I think your views about "inductance and phase-shifty current laggy problems" are usually associated with RCD's, not MCB's. An RCD (Residual Current Device) detects an imbalance between L and N by running the current through a coil... any imbalance, and it trips. It serves a different purpose to an MCB, and should be used in addition to, not instead of an MCB on normal domestic circuits - the primary purpose of an RCD being to detect current 'leakage' in ciruits used in potentially damp locations (kitchens, outside plugs, garages etc). In mains circuits dedicated to hi-fi or home cinema, the common view is to avoid using RCD's on that circuit.

If you look at the electricians handbooks (BS7671), you'll see there are tables for maximum specified trip times for all types of devices intended to disconnect a faulty circuit - fuses and MCB's - and the maximum permissible current it's allowed to pass before that device disconnects. In reality, a BS1363 13A plug fuse can pass a maximum of 26amps for a short period before it "blows", and in my experience, an MCB will usually disconnect a circuit much more quickly than a fuse. But what do I know? I'm only a humble electrician who installs dedicated mains circuits for hi-fi buffs!

A

Anonymous

Guest
  • Nov 28, 2009
  • #17

I agree with what you say Wireman.

My system is hard wired and circuit breakers are used throughout.

Also the dedicated mains spur is put through a Tacima 6 way block before feeding 2 x BT Mains conditioning units (which have built in mains reservour capacitance and isolation transformer) hence no restiction to high current flow surges.

Result ---- A totally clean power supply with a noise floor that has disapeared.

You must log in or register to reply here.

URGENT! The correct fuse in plugs.... (2024)

FAQs

URGENT! The correct fuse in plugs....? ›

It's crucial to select the right amperage for the new fuse. For lower power appliances (up to 700 watts, like lamps or mixers), a 3A fuse is needed. For higher power appliances (over 700 watts, such as microwaves and kettles), a 13A fuse is generally required.

How do you know what fuse to put in a plug? ›

An appliance that's rated up to 700 watts should be protected with a 3 amp fuse, whilst and appliance rated above 700 watts needs a 13 amp fuse. Some appliances (such as your TV) may need a 5 amp fuse, but always check the appliance manufacturer's instructions first. Make sure the fuse you use has the right rating.

What happens if you put the wrong fuse in a plug? ›

The plug with its fuse for the appliance make the minimum protection required for your piece of equipment/appliance. An incorrect fuse however will continually blow if it is incorrectly rated or fail to protect your equipment from a catastrophic meltdown if it is too high.

Can you put a 5A fuse in a 10A plug? ›

Can I put a 5A fuse in a 10A plug? - Quora. Yes. If the nominal current draw is lower than the fuse ratting. UK 13 amp plugs can be fitted with a wide range of fuses to better match the load of the thing they are fitted to.

What is the most common plug fuse? ›

Fuses come in various ratings, but the common sizes are 3 A, 5 A and 13 A. Once the current is known the next highest fuse rating is chosen. A toaster has a power rating of 750 W, 230 V.

How to choose the correct fuse? ›

All modern appliances should have the power rating marked on them. This is usually on a sticker or sometimes printed or embossed directly on the appliance. This example shows an appliance with a power rating of 1200W, so a 13A fuse should be used.

How do I know what fuse I need? ›

First, you will need to determine the maximum fuse rating in amperages by applying this formula for calculation: P (Watts) ÷ V (Voltage) = I (Amps). Next, you will need to calculate the minimum fuse rating or amperage by multiplying that total (the maximum amperage rating) by 125%.

Does it matter which way a fuse goes in a plug? ›

It definitely does matter! If the Add-A-Fuse is inserted with its ground pin in the +12V fuse panel socket, all power to the new added circuit would flow through both Add-A-Fuse fuses in series in addition to the power for the original circuit flowing through its fuse.

Is it okay to put a 5 amp fuse in a 3 amp plug? ›

If the circuit is only designed for three amps and a load draws 5A, the wires will get hot and potentially cause a fire and/or damage to the equipment. It's a bad idea. This will mean that you can load the circuit with up to 5A of device demand. Then the fuse will blow.

Can I put a bigger fuse in a plug? ›

If you replace a fuse with a higher amp fuse, especially in an appliance that is not perfectly functioning, it can lead to serious consequences. While the appliance may initially continue to work, you are taking on increased potential risks.

Can I use a 13 amp fuse in a 10 amp plug? ›

It will blow a little sooner than the 13 amp fuse would, but it would still protect the circuit. You do NOT want to go the other way and replace a 10 amp fuse with a 13 amp one. Chances are it wouldn't matter, but it would allow 3 more amps through than specified in the design. Don't do it as a continuing solution.

Which fuse is thicker 5A or 15A? ›

Therefore, 15 A fuse wire is thicker than the 5 A fuse wire.

Can I use a 5A fuse instead of 7a? ›

You can, but shouldn't. In case of 5 amp substitutions, fuse probably not large enough and will blow.

Will a plug work without a fuse? ›

The fuse is in series with the power supply, and if you remove the fuse, you have effectively disconnected the wire that provides power. No power, no work.

Is there a fuse in every plug? ›

Plugs. Most plugs will have a fuse inside them. If the appliance suddenly stops working, it is worth replacing the fuse inside the plug before calling an electrician. To find out the correct type of fuse to fit in the plug, check the rating plate on the appliance.

What are the two types of plug fuses? ›

Type-SL and Type-TL Fuses

SL and TL fuses are medium-duty time-delay fuses and are now the most commonly used plug fuses found in home electrical systems. The only difference between SL and TL fuses is the type of base: the SL fuse has a rejection base, and the TL fuse has an Edison base.

What happens if you put a 13 amp fuse in a 3 amp plug? ›

If you replace it with a 13A fuse, it may work if cable and device are in OK condition. But the protection effect is gone. If the device or the cable are defect or short circuited or similar, there may be a fire hazard. I strongly recommend to not do this.

Can you put a 5 amp fuse in a 3 amp plug? ›

If you replace it with a 5A fuse you will lose part of the protection the 3A fuse was intended to provide. In case of a failure of the device the fuse is suppose to protect, the result of using a larger fuse could be to damage the device to the extent that it could not be repaired. It could also start a fire.

How do I know which fuse to replace? ›

You should note the following when replacing fuses to ensure an exact match.
  1. Amperage rating (A). This indicates how much current the fuse can carry. ...
  2. Voltage rating (V). This is the maximum supply voltage that the fuse can safely carry. ...
  3. Blowing type. ...
  4. Size and tube material.

Can you replace a 10 amp fuse with a 13 amp fuse? ›

It will blow a little sooner than the 13 amp fuse would, but it would still protect the circuit. You do NOT want to go the other way and replace a 10 amp fuse with a 13 amp one. Chances are it wouldn't matter, but it would allow 3 more amps through than specified in the design. Don't do it as a continuing solution.

References

Top Articles
Nike Oregon Project: Der gefährliche Drang nach dem perfekten Sportlerkörper
'GMA' Deals & Steals $20 and under
Omega Pizza-Roast Beef -Seafood Middleton Menu
Mickey Moniak Walk Up Song
Melson Funeral Services Obituaries
Phcs Medishare Provider Portal
Pga Scores Cbs
The Idol - watch tv show streaming online
Emmalangevin Fanhouse Leak
Owatc Canvas
Unraveling The Mystery: Does Breckie Hill Have A Boyfriend?
Nyuonsite
Embassy Suites Wisconsin Dells
Jefferson County Ky Pva
Call of Duty: NEXT Event Intel, How to Watch, and Tune In Rewards
Jasmine
William Spencer Funeral Home Portland Indiana
What is the surrender charge on life insurance?
Hope Swinimer Net Worth
Immediate Action Pathfinder
What to do if your rotary tiller won't start – Oleomac
Www Craigslist Com Phx
Convert 2024.33 Usd
Video shows two planes collide while taxiing at airport | CNN
Golden Abyss - Chapter 5 - Lunar_Angel
Effingham Bookings Florence Sc
Axe Throwing Milford Nh
What Is Vioc On Credit Card Statement
Outlet For The Thames Crossword
yuba-sutter apartments / housing for rent - craigslist
Ltg Speech Copy Paste
A Christmas Horse - Alison Senxation
130Nm In Ft Lbs
Pdx Weather Noaa
Club Keno Drawings
Acuity Eye Group - La Quinta Photos
Nacogdoches, Texas: Step Back in Time in Texas' Oldest Town
Nextdoor Myvidster
Peter Vigilante Biography, Net Worth, Age, Height, Family, Girlfriend
2016 Honda Accord Belt Diagram
Petsmart Northridge Photos
Mydocbill.com/Mr
Search All of Craigslist: A Comprehensive Guide - First Republic Craigslist
Linda Sublette Actress
Gary Lezak Annual Salary
20 bank M&A deals with the largest target asset volume in 2023
Vindy.com Obituaries
Hovia reveals top 4 feel-good wallpaper trends for 2024
Dragon Ball Super Super Hero 123Movies
Large Pawn Shops Near Me
Premiumbukkake Tour
2000 Fortnite Symbols
Latest Posts
Article information

Author: Chrissy Homenick

Last Updated:

Views: 6450

Rating: 4.3 / 5 (74 voted)

Reviews: 89% of readers found this page helpful

Author information

Name: Chrissy Homenick

Birthday: 2001-10-22

Address: 611 Kuhn Oval, Feltonbury, NY 02783-3818

Phone: +96619177651654

Job: Mining Representative

Hobby: amateur radio, Sculling, Knife making, Gardening, Watching movies, Gunsmithing, Video gaming

Introduction: My name is Chrissy Homenick, I am a tender, funny, determined, tender, glorious, fancy, enthusiastic person who loves writing and wants to share my knowledge and understanding with you.